DSFi Series - Dual Stage Surge Filter  |
|
|
The DSFi provides secondary protection against power surges caused by external sources such as lightning strikes and substation switching as well as providing protection from surge events generated on the secondary side of the filter. Its 3-stage protection unit utilises primary and secondary MOV protection in conjunction with a Low-Q LC filter. In addition, the unit also provide filtering of the line harmonics, noise and RF transmitters.
|
Product Highlights |
|
|
Surge suppression and filtering in a single package |
|
|
Modular design |
|
|
Enclosed in IP24 steel enclosure |
|
|
Remote alarm contacts standard |
|
3 mode protection |
|
5 Year Warranty | |
|
|
|
|
DSFi Series - Dual Stage Surge Filter |
|
|
Technical Specifications
|
|
|
|
Model |
DSFi |
|
Input voltage |
200-250VAC 1phase |
|
Service type |
TT, TN, TN C-S or any single-phase system with a grounded neutral. |
|
Energy Absorption rating -per mode (Joules) |
L-N = 740 Joules, N-E = 780 Joules, Aggregate rating = 2110 JoulesPrimary Protection L-N =740 J Primary common mode protection L-E &N-E =780 J Secondary protection L-N =225J Secondary common mode protection L-E &N-E =480J Aggregate rating =2,225J |
|
Current rating – continuous |
5 - 32A |
|
Recommended max. over current protection |
32A (C curve MCCB) |
|
Short circuit withstand (1 sec) |
Suitable for use with a 6kAIC C Curve MCB |
|
Protection modes |
Line-Neutral, Line-Earth, Neutral-Earth |
|
In 8/20us (Line-Neutral) |
15kA x 20 hits |
|
In 8/20us (Line-Earth) |
10kA x 20 hits |
|
In 8/20us (Neutral-Earth) |
10kA x 20 hits |
|
Ismax 8/20us (Line-Neutral) |
50kA |
|
Ismax 8/20us (Line-Earth) |
25kA |
|
Ismax 8/20us (Neutral-Earth) |
25kA |
|
Filter attenuation |
> 80dB to 10MHz |
|
Internal protection (fusing) |
Thermal |
|
Terminations |
10mm2 PCB Mounted Terminals |
|
Alarms/indicators |
2 LED display,Power OK &Protection OK LEDs,Dry contact alarm relay output – 250Vac//32Vdc,5A,5kV isolation, Alarm under-voltage cutoff 180Vac |
|
Enclosure rating |
IP24 |
|
Design Standards: |
IEC61643-1, IEC610006-1,2,3,4 ANSI/IEEE C62.41 Cat B,C,D,E AS1768-1991 Cat B,C,D,E AS3000,AS3100, CE mark |
|
Dimension |
|
|
Environment |
C, 10 to 90%RH (non-condensing)°-10 to 65 |
Price $565.00 inc gst , plus delivery
Does not include installation